Ürün Tanımı

H3DT

Detaylar

Pano içi uygulamalara yönelik Push-in Plus
teknolojili 17,5 mm genişliğinde ince zaman röleleri

  • Yerden tasarruf sağlamaya ve kontrol panoları için gereken işçiliği azaltmaya yardımcı olur.
  • İki kontak setli ince zaman röleleri (17,5 mm genişliğinde): Dünyanın en ince zaman rölelerinden biridir.
  • Güç tüketimini (aktif güç) % 60'a varan oranda azaltarak kontrol panolarındaki ısı oluşumunu azaltmaya yardımcı olur.
  • Denizcilik standartları (LR/DNV GL) onaylıdır.
  • RoHS uyumluluğu

Ordering information

Type

Supply voltage

Operating modes

Terminal block

Input type

Control output

Time range

Order code

Multi-range, multi-mode standard timer

24 to 240 VAC/DC

A2 : ON Delay (Power ON Delay)

B3 : Flicker OFF Start (Power ON Start)

B4 : Flicker ON Start (Power ON Start)

D : Signal OFF Delay

E2 : Interval (Power ON Start)

E3 : Signal OFF Interval

F2 : Cumulative (ON Delay)

F3 : Cumulative (Interval)

10 terminals

Voltage input

Relay, DPDT

0.1 s to 1,200 h

H3DT-N2

8 terminals

Relay, SPDT

H3DT-N1

Multi-range, multi-mode expansion timer

A : ON Delay (Signal ON Delay)

B : Flicker OFF Start (Signal Start)

B2 : Flicker ON Start (Signal Start)

C : Signal ON/OFF Delay

E : Interval (Signal Start)

G : Signal ON/OFF Delay

J : One-shot Output (Signal Start)

J2 : One-shot Output (Power ON Start)

10 terminals

Relay, DPDT

H3DT-L2

8 terminals

Relay, SPDT

H3DT-L1

Power ON-delay timer

24 to 240 VAC/DC

Power ON-delay

8 terminals

-

Relay, DPDT

0.1 s to 1,200 h

H3DT-A2

6 terminals

Relay, SPDT

H3DT-A1

Twin timer

24 to 240 VAC/DC

Flicker OFF start/flicker ON start

6 terminals

-

Relay, SPDT

0.1 s to 1,200 h

H3DT-F

Star-delta timer

24 to 240 VAC/DC

Time-limit operation/self-resetting

8 terminals

-

Relay, Time-limit

Star circuit, SPDT

Delta circuit, SPDT

1 to 120 s

4
4. Star set time (t1) range. Star-Delta transfer time (t2): Select from 0.05, 0.1, 0.25, or 0.5 s

H3DT-G

Power OFF-delay Timer

100 to 120 VAC

Instantaneous operation/time-limit reset

6 terminals

-

Relay, SPDT

0.1 to 12 s

H3DT-HCS

200 to 240 VAC

H3DT-HDS

24 to 48 VAC/DC

H3DT-HBS

100 to 120 VAC

1 to 120 s

H3DT-HCL

200 to 240 VAC

H3DT-HDL

24 to 48 VAC/DC

H3DT-HBL

Specifications

 

H3DT

-N2/-L2

-N1/-L1

-A2

-A1

-F

-G

-HCS

-HCL

-HDS

-HDL

-HBS/-HBL

Power supply voltage

24 to 240 VAC/DC, 50/60 Hz

5
5. When using a 24 VDC power supply voltage, there will be an inrush current of approximately 0.5 A. Allow for this inrush current when turning ON and OFF the power supply to the Timer with device with a solid-state output, such as a sensor.
,
6
6. DC ripple: 20% max.

100 to 120 VAC, 50/60 Hz

200 to 240 VAC, 50/60 Hz

24 to 48 VAC/DC, 50/60 Hz

2
6. DC ripple: 20% max.

Allowable voltage fluctuation range

85% to 110% of rated voltage

Power reset

Minimum power-OFF time: 0.1 s

-

Reset voltage

10% of rated voltage

-

Voltage input

24 to 240 VAC/DC
High level:
20.4 to 264 VAC/DC,
Low level: 0 to 2.4 VAC/DC

-

Power consumption

At 240 VAC: 2.3 VA max.,
at 240 VDC: 1.0 W max.,
at 24 VDC: 0.3 W max.

7
7. The power consumption is the value after the timer times out.

At 240 VAC: 2.0 VA max.,
at 240 VDC: 0.9 W max.,
at 24 VDC: 0.3 W max.

3
7. The power consumption is the value after the timer times out.

At 240 VAC: 2.2 VA max.,
at 240 VDC: 0.7 W max.,
at 24 VDC: 0.3 W max.

3
7. The power consumption is the value after the timer times out.

At 240 VAC: 1.8 VA max.,
at 240 VDC: 0.6 W max.,

at 24 VDC: 0.3 W max.

3
7. The power consumption is the value after the timer times out.

At 240 VAC: 1.9 VA max.,
at 240 VDC: 0.6 W max.,
at 24 VDC: 0.3 W max.

At 120 VAC: 8.7 VA max.

At 120 VAC: 8.8 VA max.

At 240 VAC: 21.6 VA max.

At 240 VAC: 21.7 VA max.

At 48 VAC: 1.0 VA max.,
at 24 VDC: 0.4 W max.

Control output

Contact output:

  • 5 A at 250 VAC with resistive load (cosφ = 1),
  • 5 A at 30 VDC with resistive load,
  • 0.15 A max. at 125 VDC with resistive load,
  • 0.1A max. at 125 VDC with L/R of 7 ms.

The minimum applicable load is 10 mA at 5 VDC (P reference value).

Contact materials: Ag-alloy

(Recommended fuse: BLN5 (Littelfuse) or 0216005MXEP)

Ambient temperature

Operating: -20 to 60°C (with no icing)

Storage: -40 to 70°C (with no icing)

Accuracy of operating time

±1% of FS max. (±1% ±10 ms max. at 1.2 s range)

±1% of FS max.

±1% of FS max. (±1% ±10 ms max. at 1.2 s range)

Setting error

±10% of FS ±0.05 s max.

Influence of voltage

±0.5% of FS max. (±0.5% ±10 ms max. at 1.2 s range)

±0.5% of FS max.

±0.5% of FS max. (±0.5% ±10 ms max. at 1.2 s range)

Influence of temperature

±2% of FS max. (±2% ±10 ms max. at 1.2 s range)

±2% of FS max.

±2% of FS max. (±2% ±10 ms max. at 1.2 s range)

Life expectancy

Mechanical: 10 million operations min. (under no load at 1,800 operations/h)

Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)

Degree of protection

IP30 (Terminal block: IP20)

Size in mm (H × W × D)

100×17.5×90


1. According to OMRON investigation in October 2015.

2. Based on OMRON comparison (excluding the H3DT-H).

3. Certification is pending for DNV GL.

4. Star set time (t1) range. Star-Delta transfer time (t2): Select from 0.05, 0.1, 0.25, or 0.5 s

5. When using a 24 VDC power supply voltage, there will be an inrush current of approximately 0.5 A. Allow for this inrush current when turning ON and OFF the power supply to the Timer with device with a solid-state output, such as a sensor.

6. DC ripple: 20% max.

7. The power consumption is the value after the timer times out.

-