Ürün Tanımı

G3PA

Detaylar

Değiştirilebilir güç kartuşlu Solid State Röleler

Soğutucunun optimum dizaynı sayesinde ufaltılmış boyut. G3PA'nın güç eleman kartuşları kolay bakım için kolayca değiştirilebilir. G3PA DIN raya ya da vidalarla monte edilebilir.

  • 20-60 A çıkış akımı
  • 24-480 VAC çıkış gerilimi
  • 3 faz yüklere uygulanabilir
  • Değiştirilebilen güç eleman kartuşları

Ordering information

Rated output load

Zero cross function

Rated input voltage

Operating voltage range

Input
current impedance

Voltage level

Size in mm
(H×W×D)

Order code

Must operate voltage

Must release voltage

24 to 240 VAC

40 A

Yes

5 to 24 VDC

4 to 30 VDC

7 mA max.

4 VDC max.

1 VDC min.

100×47×100

G3PA-240B-VD DC5-24

60 A

 

100×110×100

G3PA-260B-VD DC5-24

40 A

 

24 VAC

19.2 to 26.4 VAC

1.4 kΩ ±20%

19.2 VAC max.

4.8 VAC min.

100×47×100

G3PA-240B-VD AC24

60 A

 

100×110×100

G3PA-260B-VD AC24

180 to 400 VAC

20 A

 

12 to 24 VDC

9.6 to 30 VDC

7 mA max.

9.2 VDC max.

1 VDC min.

100×37×100

G3PA-420B-VD DC12-24

30 A

 

100×47×100

G3PA-430B-VD DC12-24

200 to 480 VAC

20 A

 

100×37×100

G3PA-420B-VD-2 DC12-24

30 A

 

100×47×100

G3PA-430B-VD-2 DC12-24

50 A

 

100×110×100

G3PA-450B-VD-2 DC12-24

Accessories

 

Replacement parts: Power device cartridges

Load voltage range

Carry current

Applicable SSR

Order code

19 to 264 VAC

40 A

G3PA-240B-VD DC5-24

G32A-A40-VD DC5-24

G3PA-240B-VD AC24

G32A-A40-VD AC24

60 A

G3PA-260B-VD DC5-24

G32A-A60-VD DC5-24

G3PA-260B-VD AC24

G32A-A60-VD AC24

150 to 440 VAC

20 A

G3PA-420B-VD DC12-24

G32A-A420-VD DC12-24

30 A

G3PA-430B-VD DC12-24

G32A-A430-VD DC12-24

180 to 528 VAC

20 A

G3PA-420B-VD-2 DC12-24

G32A-A420-VD-2 DC12-24

30 A

G3PA-430B-VD-2 DC12-24

G32A-A430-VD-2 DC12-24

50 A

G3PA-450B-VD-2 DC12-24

G32A-A450-VD-2 DC12-24

 

G32A-D__ enables 2 line switching of 3 phase configurations

Current flow

Applicable SSR

Order code

20 A

G3PA-420B-VD, G3PA-420B-VD-2

G32A-D20

30 A

G3PA-430B-VD, G3PA-430B-VD-2,
G3PA-240B-VD, G3PA-240BL-VD

G32A-D40

40 A

Specifications

Isolation

Phototriac coupler

Indicator

Yes

Ambient temperature

Operating: −30 to 80°C

Load voltage range

200 to 480 VAC: 180 to 528 VAC

24 to 240 VAC: 19 to 264 VAC

180 to 400 VAC: 150 to 440 VAC

Output ON drop

1.6 V (RMS) max.

Operate time

0.5 of load power source cycle + 1 ms max. (DC input, -B models)

1.5 of load power source cycle + 1 ms max. (AC input)
1 ms max. (-BL models)

Release time

0.5 of load power source cycle + 1 ms max. (DC input)

1.5 of load power source cycle + 1 ms max. (AC input)

-