G9SE

Detaylar

İnce boyutlu güvenlik röle birimi ailesi

G9SE ailesi E-Stop, kapı ve güvenlik izlemesi uygulamaları için kompakt birimler sunar. İnce gövde içinde iki veya dört güvenlik kontaklı ve KAPATMA gecikme zamanlamalı modüller mevcuttur.

  • Vidasız terminallerle kolay önden kablolama.
  • Montaj alanından kazanmak için 17,5 veya 22,5 mm genişlik
  • 15 ms Maks. yanıt süresi
  • PLe'ye kadar emniyetli KAPATMA gecikmesi fonksiyonu
  • EN 81-1, EN 81-2 asansör standartları için sertifika
  • EN ISO 13849-1'e uygun şekilde Ple'ye, EN 61508'e uygun şekilde SIL 3'e kadar

Ordering information

Safety outputs

Auxiliary outputs

1
1. PNP transistor output

Max. OFF-delay time

2
2. The OFF-delay time can be set in 16 steps as follows:
T05: 0/0.1/0.2/0.3/0.4/0.5/0.6/0.7/0.8/1/1.5/2/2.5/3/4/5 s
T30: 0/1/2/4/5/6/7/8/9/10/12/14/16/20/25/30 s

Rated voltage

Order code

Instantaneous

OFF-delayed

DPST-NO

-

1 PNP transistor output

-

24 VDC

G9SE-201

4PST-NO

G9SE-401

DPST-NO

DPST-NO

5 s

G9SE-221-T05

DPST-NO

DPST-NO

30 s

G9SE-221-T30

Specifications

Ratings

Power Input

Item

G9SE-201

G9SE-401

G9SE-221-T _

Rated supply voltage

24 VDC

Operating voltage range

-15% to 10% of rated supply voltage

Rated power consumption

3
3. Power consumption of loads not included.

3 W max.

4 W max.

 

Outputs

Item

G9SE-201

G9SE-401

G9SE-221-T _

Safety output

OFF-delayed safety output

Contact output

250 VAC 5 A 30 VDC 5 A (resistance load)

Auxiliary output

PNP transistor output Load current: 100 mA DC max.

 

Characteristics

Item

G9SE-201

G9SE-401

G9SE-221-T _

Operating time (OFF to ON state)

4
4. The operating time is the time it takes for the safety contact to close after the safety inputs and feedback-reset input are turned ON. Not including bounce time.

100 ms Max.

5
5. This is in normal operation. When executing non-regular self-diagnosis for Safety output circuit, G9SE operating time become 500 ms max..

Response time (ON to OFF state)

6
6. The response time is the time it takes for the safety main contact to open after the safety input is turned OFF. Includes bouncetime.

15 ms Max.

Inputs

Input current

5 mA Min.

ON voltage

11 VDC Min.

OFF voltage

5 VDC Max.

OFF current

1 mA Max.

Maximum cable length

100 m Max.

Reset input time

250 ms Min.

Contact outputs

Contact resistance

7
7. This is initial value using the voltage-drop method with 1 A at 5 VDC.

100 m Ω

Mechanical durability

5,000,000 operations Min.

Electrical durability

50,000 operations Min.

Switching specification Inductive load

(IEC/EN60947-5-1)

AC15: 240 VAC 2 A

DC13: 24 VDC 1.5 A

Minimum applicable load

24 VDC 4 mA

Conditional short-circuit current

(IEC/EN60947-5-1)

100A

8
8. Use an 8 A fuse that conforms to IEC 60127 as a short-circuit protection device. This fuse is not included with the G9SE.

Surrounding air temperature

-10 to 55 ° C (No freezing or condensation)


1. PNP transistor output

2. The OFF-delay time can be set in 16 steps as follows:
T05: 0/0.1/0.2/0.3/0.4/0.5/0.6/0.7/0.8/1/1.5/2/2.5/3/4/5 s
T30: 0/1/2/4/5/6/7/8/9/10/12/14/16/20/25/30 s

3. Power consumption of loads not included.

4. The operating time is the time it takes for the safety contact to close after the safety inputs and feedback-reset input are turned ON. Not including bounce time.

5. This is in normal operation. When executing non-regular self-diagnosis for Safety output circuit, G9SE operating time become 500 ms max..

6. The response time is the time it takes for the safety main contact to open after the safety input is turned OFF. Includes bouncetime.

7. This is initial value using the voltage-drop method with 1 A at 5 VDC.

8. Use an 8 A fuse that conforms to IEC 60127 as a short-circuit protection device. This fuse is not included with the G9SE.

-