Ordering information
SX
Specifications
|
Order code
|
Voltage
|
Heavy duty
|
Normal duty
|
IP54 model
|
IP20 model
|
Direct torque control
|
V/F
|
Direct torque control
|
V/F
|
690 V
|
75 kW
|
72 A
|
90 kW
|
90 A
|
SX-D6090-EF
|
SX-D6090-EV
|
-
|
-
|
90 kW
|
87 A
|
110 kW
|
109 A
|
SX-D6110-EF
|
SX-D6110-EV
|
110 kW
|
117 A
|
132 kW
|
146 A
|
SX-D6132-EF
|
SX-D6132-EV
|
132 kW
|
140 A
|
160 kW
|
175 A
|
SX-D6160-EF
|
SX-D6160-EV
|
160 kW
|
160 A
|
200 kW
|
200 A
|
SX-D6200-E1F
|
SX-D6200-E1V
|
200 kW
|
200 A
|
250 kW
|
250 A
|
SX-D6250-E1F
|
SX-D6250-E1V
|
SX-A6250-EF
|
SX-A6250-EV
|
250 kW
|
240 A
|
315 kW
|
300 A
|
SX-D6315-E1F
|
SX-D6315-E1V
|
SX-A6315-EF
|
SX-A6315-EV
|
315 kW
|
300 A
|
355 kW
|
375 A
|
SX-D6355-E1F
|
SX-D6355-E1V
|
SX-A6355-EF
|
SX-A6355-EV
|
315 kW
|
344 A
|
450 kW
|
430 A
|
SX-D6450-E1F
|
SX-D6450-E1V
|
SX-A6450-EF
|
SX-A6450-EV
|
355 kW
|
400 A
|
500 kW
|
500 A
|
SX-D6500-E1F
|
SX-D6500-E1V
|
SX-A6500-EF
|
SX-A6500-EV
|
450 kW
|
480 A
|
600 kW
|
600 A
|
SX-D6600-E1F
|
SX-D6600-E1V
|
SX-A6600-EF
|
SX-A6600-EV
|
500 kW
|
520 A
|
630 kW
|
650 A
|
SX-D6630-E1F
|
SX-D6630-E1V
|
SX-A6630-EF
|
SX-A6630-EV
|
600 kW
|
576 A
|
710 kW
|
720 A
|
SX-D6710-E1F
|
SX-D6710-E1V
|
SX-A6710-EF
|
SX-A6710-EV
|
650 kW
|
640 A
|
800 kW
|
800 A
|
SX-D6800-E1F
|
SX-D6800-E1V
|
SX-A6800-EF
|
SX-A6800-EV
|
710 kW
|
720 A
|
900 kW
|
900 A
|
SX-D6900-E1F
|
SX-D6900-E1V
|
SX-A6900-EF
|
SX-A6900-EV
|
800 kW
|
800 A
|
1,000 kW
|
1,000 A
|
SX-D61K0-E1F
|
SX-D61K0-E1V
|
SX-A61K0-EF
|
SX-A61K0-EV
|
A
Panel kit
Type
|
Description
|
Function
|
Order code
|
Panel kit
|
Panel kit
|
Complete panel kit including operator
|
SX-OP02-00-E
|
Blank panel kit
|
Complete panel kit including a blank operator
|
SX-OP02-01-E
|
Operator
|
Handheld control panel
|
Complete handheld control panel
|
SX-OPHH-00-E
|
Digital operator
|
Inverter digital operator
|
SX-OP01-00-E
|
Blank operator
|
Blank operator
|
SX-OP01-11-E
|
②
I/O option board
Description
|
Function
|
Order code
|
Additional I/O option
|
Provides 3 extra relay outputs and 3 additional digital inputs
|
01-3876-01
|
Crane option
|
Dedicated option board for crane application, including additional I/O and functions
|
01-3876-07
|
③
Communication option board
Description
|
Function
|
Order code
|
RS232/485
|
MODBUS RTU serial communication by RS232 or RS485 interface with galvanic isolation
|
01-3876-04
|
PROFIBUS-DP
|
Used for operating the inverter through PROFIBUS-DP communication with the host controller
|
01-3876-05
|
DeviceNet
|
Used for operating the inverter through DeviceNet communication with the host controller
|
01-3876-06
|
Modbus/TCP, Ethernet
|
Used for operating the inverter through Modbus/TCP communication with the host controller
|
01-3876-09
|
EtherCAT
|
Used for operating the inverter through EtherCAT communication with the host controller
|
01-3876-10
|
PROFINET (1-port)
|
Used for operating the inverter through PROFINET communication with the host controller
|
01-3876-11
|
PROFINET (2-ports)
|
01-3876-12
|
④
Encoder feedback option card
Description
|
Function
|
Order code
|
Encoder option
|
Used for connection of the actual motor speed via encoder.
Up to 100 kHz with TTL and HTL incremental encoders with 5/24 V power supply
|
01-3876-03
|
⑤
PTC/PT100 option card
Description
|
Function
|
Order code
|
Thermal protection
|
Allows to connect a motor thermistor to the inverter
|
01-3876-08
|
⑥
Braking chopper and braking resistor
All inverter sizes could be fitted with an optional built-in brake chopper from factory but is not possible to install it later. The choice of the resistor depends on the application switch-on duration and duty-cycle. Following tables describes the activation level of the built-in braking chopper and the minimum resistor that could be used depending on the input voltage.
Rmin for different input voltage (
Ω)
|
Order code
|
500-525 VAC
|
550-600 VAC
|
660-690 VAC
|
4.9
|
5.7
|
6.5
|
SX-D6090-EF
|
4.9
|
5.7
|
6.5
|
SX-D6110-EF
|
4.9
|
5.7
|
6.5
|
SX-D6132-EF
|
4.9
|
5.7
|
6.5
|
SX-D6160-EF
|
2 × 4.9
|
2 × 5.7
|
2 × 6.5
|
SX-D6200-EF
|
2 × 4.9
|
2 × 5.7
|
2 × 6.5
|
SX-D6250-EF
|
2 × 4.9
|
2 × 5.7
|
2 × 6.5
|
SX-D6315-EF
|
2 × 4.9
|
2 × 5.7
|
2 × 6.5
|
SX-D6355-EF
|
3 × 4.9
|
3 × 5.7
|
3 × 5.7
|
SX-D6450-EF
|
3 × 4.9
|
3 × 5.7
|
3 × 5.7
|
SX-D6500-EF
|
4 × 4.9
|
4 × 5.7
|
4 × 5.7
|
SX-D6600-EF
|
4 × 4.9
|
4 × 5.7
|
4 × 5.7
|
SX-D6630-EF
|
6 × 4.9
|
6 × 5.7
|
6 × 5.7
|
SX-D6710-EF
|
6 × 4.9
|
6 × 5.7
|
6 × 5.7
|
SX-D6800-EF
|
6 × 4.9
|
6 × 5.7
|
6 × 5.7
|
SX-D6900-EF
|
6 × 4.9
|
6 × 5.7
|
6 × 5.7
|
SX-D61K0-EF
|
Supply voltage (VAC)
|
Built-in brake chopper trigger level (VDC)
|
500-525
|
860
|
550-600
|
1,000
|
660-690
|
1,150
|
⑦
Output coils
Output coils above SX-D4132-E should be order from factory as they should be installed inside of the cabinet
Voltage
|
Inverter model
|
Rated current
|
Inductance
|
Rated voltage
|
Max carrier
|
Max. output frequency
|
Max. temp
|
Order code
|
690 V
|
SX-D6090-EF
|
90 A
|
0.1 mH
|
800 V
|
6 kHz
|
200 Hz
|
40ºC
|
473169 00
|
SX-D6110-EF
|
146 A
|
0.05 mH
|
6 kHz
|
200 Hz
|
473170 00
|
SX-D6132-EF
|
SX-D6160-EF
|
175 A
|
0.05 mH
|
6 kHz
|
200 Hz
|
473171 00
|
⑧
Overshoot clamp
Note: Only two types of overshoot clamps could be order for after mounting
Inverter
|
Function
|
Order code
|
SX-6090 to SX-6160
|
Together with the output coils, the overshoot clamp restricts the voltage and the dV/dt on the motor winding.
Inverters must be ordered including the option DC'DC- connectors.
|
52163
|
SX-6200 to SX-61K0
|
Together with the output coils, the overshoot clamp restricts the voltage and the dV/dt on the motor winding.
Doesn´t require the “DC'DC-” option.
|
52220
|
Computer software
Installation
|
Order code
|
Configuration and monitoring software tool
|
CX-Drive
|
Configuration and monitoring software tool
|
CX-One
|
Software tool for energy saving calculation
|
€Saver
|
Specifications
Three-phase: SX-_6__-E_
|
90
|
110
|
132
|
160
|
200
|
250
|
315
|
355
|
450
|
500
|
600
|
630
|
710
|
800
|
900
|
1K0
|
Motor
kW
|
For HD setting
|
75
|
90
|
110
|
132
|
160
|
200
|
250
|
315
|
315
|
355
|
450
|
500
|
600
|
650
|
710
|
800
|
For ND setting
|
90
|
110
|
132
|
160
|
200
|
250
|
315
|
355
|
450
|
500
|
600
|
630
|
710
|
800
|
900
|
1,000
|
Output
characteristics
|
Max output current (A)
|
108
|
131
|
175
|
210
|
252
|
300
|
360
|
450
|
516
|
600
|
720
|
780
|
900
|
1,032
|
1,080
|
1,200
|
Rated output current (A) at HD
|
72
|
87
|
117
|
140
|
160
|
200
|
240
|
300
|
344
|
400
|
480
|
520
|
576
|
640
|
720
|
800
|
Rated output current (A) at ND
|
90
|
109
|
146
|
175
|
200
|
250
|
300
|
375
|
430
|
500
|
600
|
650
|
720
|
800
|
900
|
1,000
|
Output voltage
|
0 to Mains supply voltage
|
Max. output frequency
|
400 Hz
|
Power
supply
|
Rated input voltage and frequency
|
3-phase 500 to 690 V, 50/60 Hz
|
Allowable voltage fluctuation
|
10% to -15%
|
Allowable frequency fluctuation
|
45 to 65 Hz
|
Dimensions
Degree of protection
|
Drive model
|
H
|
W
|
D
|
|
IP20
|
SX-A6250 to SX-A6355
|
1,176
|
500
|
450
|
|
SX-A6450 to SX-A6600
|
1,176
|
730
|
450
|
SX-A6630 to SX-A6800
|
1,176
|
1,100
|
450
|
SX-A6900 to SX-A61K0
|
1,176
|
1,365
|
450
|
IP54
|
SX-D6090 to SX-D6200
|
952.5
|
344.5
|
314
|
SX-D6250 to SX-D6355
|
2,250
|
600
|
600
|
SX-D6450 to SX-D6600
|
2,250
|
900
|
600
|
SX-D6630 to SX-D6800
|
2,250
|
1,200
|
600
|
SX-D6900 to SX-D61K0
|
2,250
|
1,500
|
600
|