Three-phase: CIMR-UC4E_
|
0011
|
0014
|
0021
|
0027
|
0034
|
0040
|
0052
|
0065
|
0077
|
0096
|
0124
|
0156
|
0180
|
0216
|
0240
|
0302
|
0361
|
0414
|
In/Out characteristics
|
Input current at HD
|
A
|
8.7
|
10
|
13
|
19
|
25
|
31
|
36
|
47
|
59
|
70
|
87
|
113
|
142
|
164
|
197
|
218
|
275
|
329
|
Input current at ND
|
A
|
10
|
13
|
19
|
25
|
31
|
36
|
47
|
59
|
70
|
87
|
113
|
142
|
164
|
197
|
218
|
275
|
329
|
377
|
Rated input capacity at HD
|
kVA
|
8
|
9
|
12
|
17
|
22
|
28
|
33
|
43
|
54
|
64
|
80
|
103
|
130
|
150
|
180
|
200
|
251
|
300
|
Rated input capacity at ND
|
kVA
|
9
|
12
|
17
|
22
|
28
|
33
|
43
|
54
|
64
|
80
|
103
|
130
|
150
|
180
|
200
|
251
|
300
|
344
|
Rated output current at HD
|
A
|
9.6
|
11
|
14
|
21
|
27
|
34
|
40
|
52
|
65
|
77
|
96
|
124
|
156
|
180
|
216
|
240
|
302
|
361
|
Rated output current at ND
|
A
|
11
|
14
|
21
|
27
|
34
|
40
|
52
|
65
|
77
|
96
|
124
|
156
|
180
|
216
|
240
|
302
|
361
|
414
|
Overload tolerance
|
%
|
HD rating: 150% of rated output current for 60 s
ND rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
|
Output voltage
|
V
|
0 to Mains supply voltage
|
Carrier frequency
|
Hz
|
4 KHz (user adjustable up to 10 KHz. Derating may be required)
|
Max. output frequency
|
Hz
|
400 Hz
|
Power
supply
|
Rated input voltage and frequency
|
Three-phase 380 to 480 VAC, 50/60 Hz
|
Allowable voltage fluctuation
|
-15% to +10%
|
Allowable frequency fluctuation
|
±3% (frequency fluctuation rate: 1 Hz/100 ms or less)
|
Harmonics current distortion, THDI
|
< 5% (IEEE519 compliant)
|
Input power factor
|
0.98 min (during rated operation)
|
Efficiency
|
> 96%
|
Weight with IP00 protection
|
kg
|
21
|
33
|
36
|
63
|
115
|
181
|
267
|
Weight with IP20 protection
|
kg
|
22.5
|
35
|
38
|
65
|
118
|
185
|
278
|