Item
|
15 W
|
30 W
|
60 W
|
120 W
|
240 W
|
480 W
|
Efficiency (Typ. at 230 VAC)
|
80% (24 V)
|
86% (24 V)
|
88% (24 V)
|
89% (24 V)
|
92% (24 V)
|
93% (24 V)
|
Input
|
Rated input voltage
|
100 to 240 VAC
|
Allowable range
|
85 to 264 VAC, 90 to 350 VDC. 2 phases less than 240 VAC
|
Output
|
Voltage adjustment range (with V.ADJ)
|
-10% to 15%
|
Input variation influence
|
0.5% max. (at 85 to 264 VAC input, 100% load)
|
Load variation Influence
|
3.0% max. (5 V), 2.0% max. (12 V), 1.5% max. (24, 48 V), at 0% to 100% load
|
Temperature variation influence
|
0.05%/°C max.
|
Overload protection
|
Yes, 130% of rated current typ.
|
Power Boost
|
120% of rated current
|
Overvoltage protection
|
Yes
|
Operating ambient temperature
|
−40 to 70°C (−40 to 158°F)
|
Series operation
|
Yes, up to 2 units
|
Parallel operation
|
Yes, up to 2 units
|
EMI
|
Conforms to EN 61204-3, EN 55011 Class B
|
EMS
|
Conforms to EN 61204-3 high severity levels
|
Harmonic current emissions
|
Conforms to EN 61000-3-2
|
Approved standards
|
UL: UL 508 (Listing), UL 60950-1, cUL: CSA C22.2 No. 107.1 and No. 60950-1,
UL 1310 Class 2 output for 15 W, 30 W, 60 W
EN/VDE: EN 50178 (=VDE0160), EN 60950-1 (=VDE0805),
Lloyd’s Register
ANSI/ISA 12.12.01
|
Fulfilled standards
|
SELV (EN 60950-1/EN 50178/UL 60950-1), PELV(EN 60204-1,EN 50178),
Safety of power transformers (EN 61558-2-16), EN 50274 for terminal parts
|
Degree of protection
|
IP20 by EN/IEC 60529
|