Item
|
15 W
|
35 W
|
50 W
|
100 W
|
150 W
|
300 W
|
600 W
|
Efficiency (Typ. at 230 VAC)
|
81% (24 V)
|
84% (24 V)
|
86% (24 V)
|
88% (24 V)
|
90% (24 V)
|
88% (24 V)
|
84% (24 V)
|
Input
|
Rated input voltage
|
100 to 240 VAC
|
100 to 120 VAC/200 to 240 VAC, Switchable
|
Allowable range
|
85 to 264 VAC, 80 to 370 VDC (DC is not applicable for the safety standards.)
|
85 to 132 VAC/170 to 264 VAC
|
Output
|
Voltage adjustment range (with V.ADJ)
|
−10% to 15% for 5 V to 24 V, ±10% for 48 V (with V.ADJ)
|
Input variation influence
|
0.4% max. (at 85 to 264 VAC input, 100% load)
|
Load variation Influence
|
0.8% max. at 0% to 100% load
|
Temperature variation influence
|
0.05%/°C max.
|
Overload protection
|
Yes, 105% to 160% of rated current
|
Overvoltage protection
|
Yes
|
Operating ambient temperature
|
−10 to 60°C (14 to 140°F)
|
Series operation
|
Yes, up to 2 units
|
Yes, up to 2 units
|
Parallel operation
|
No
|
Yes, up to 5 units
|
EMI
|
Conforms to EN 61204-3, EN 55011 Class A
|
EMS
|
Conforms to EN 61204-3 high severity levels
|
Approved standards
|
UL: UL 508 (Listing), UL 60950-1, cUL: CSA C22.2 No. 107.1 and No. 60950-1,
EN/VDE: EN 50178 (=VDE0160), EN 60950-1 (=VDE0805)
|
UL: UL 508 (Recognition), UL 60950-1,
cUR: CSA C22.2 No. 107.1 and No. 60950-1,
EN/VDE: EN 50178 (=VDE0160), EN 60950-1 (=VDE0805)
|
Fulfilled standards
|
EN 50274 for terminal parts
|