Item
|
E5CSV
|
Supply voltage
|
100 to 240 VAC, 50/60 Hz or 24 VAC/VDC (depending on model)
|
Operating voltage range
|
85 to 110% of rated supply voltage
|
Power consumption
|
5 VA
|
Sensor input
|
Multi-input (thermocouple/platinum resistance thermometer): K, J, L, T, U, N, R, Pt100, JPt100
|
Control output
|
Relay output
|
SPST-NO, 250 VAC, 3 A (resistive load)
|
Voltage output (for driving SSR)
|
12 VDC, 21 mA (with short-circuit protection circuit)
|
Control method
|
ON/OFF or 2-PID (with auto-tune and self-tune)
|
Alarm output
|
SPST-NO, 250 VAC, 1 A (resistive load)
|
Setting method
|
Digital setting using front panel keys (functionality set-up with DIP switch)
|
Indication
|
7-segment digital display (character height: 13.5 mm) and deviation indicators
|
Ambient temperature
|
-10 to 55°C (with no condensation or icing)
|
Setting/indication accuracy
|
±0.5% of indication value or ±1 °C, whichever is greater ±1 digit max.
|
Hysteresis (for ON/OFF control)
|
0.2% FS (0.1% FS for multi-input (thermocouple/platinum resistance thermometer) models)
|
Proportional band (P)
|
1 to 999°C (automatic adjustment using AT/ST)
|
Integral time (I)
|
0 to 1,999 s (automatic adjustment using AT/ST)
|
Derivative time (D)
|
0 to 1,999 s (automatic adjustment using AT/ST)
|
Control period
|
2/20 s
|
Sampling period
|
500 ms
|
Electrical life expectancy
|
100,000 operations min. (relay output models)
|
Weight
|
Approx. 120 g (controller only)
|
Degree of protection
|
Front panel: Equivalent to IP66; rear case: IP20; terminals: IP00
|
Memory protection
|
EEPROM (non-volatile memory) (number of writes: 1,000,000)
|
Size in mm (H×W×D)
|
48×48×78
|