Item
|
E5CB
|
Power supply voltage
|
100 to 240 VAC 50/60 Hz, 24 VAC 50/60 Hz, or 24 VDC
|
Operating voltage range
|
85% to 110% of rated supply voltage
|
Power consumption
|
Approx. 3.5 VA (100 to 240 VAC)
Approx. 3.5 VA (24 VAC)
Approx. 2.5 W (24 VDC)
|
Sensor input
|
Models with thermocouple inputs
Thermocouple: K, J, T, R, or S (JIS C 1602-1995, IEC60584-1)
|
Models with platinum resistance thermometer inputs
Platinum resistance thermometer: Pt100 (JIS C 1604-1997, IEC60751)
|
Control output
|
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
minimum applicable load: 5 V, 10 mA
|
Output voltage: 12 VDC +25%/−15% (PNP), max. load current: 21 mA, with short-circuit protection circuit
|
Alarm output
|
SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA
|
Control method
|
ON/OFF control or 2-PID control (with auto-tuning)
|
Setting method
|
Digital setting using front panel keys
|
Indication method
|
7-segment digital display and individual indicators
Character height: 16.2 mm (PV)
|
Other functions
|
Temperature input shift, run/stop, protection functions, etc.
|
Ambient operating
temperature
|
−10 to 55°C (with no condensation or icing)/With a three-year guarantee: −10 to 50°C
|
Ambient operating humidity
|
25% to 85%
|
Storage temperature
|
−25 to 65°C (with no condensation or icing)
|
Size in mm (H × W × D)
|
48×48×65
|